085 501 949j 30320-004j 3
PY X-S-05 – Beacon
Operating and installation instruction
Dimensions
Ø6.3 [0.25]
22 [0.87"]
80.6 [3.17]
109.6 [4.31]
98 [3.86]
86 [3,385]
prepared
M20 piercing
37 [1.46"]
Technical Data
Flash energy 5J
Rated effective luminous
intensity
44 cd (clear)
Flash frequency 1Hz
Rated voltage 12 V DC 24V DC 48V DC
24V AC
50/60 Hz
115 V AC, 50/60
Hz
230V AC
50/60 Hz
Operating voltage range 10 –15 V DC 18 – 30 V DC 40 – 57 V DC 18 – 30 V AC
95 - 127
V AC
195 – 253 V AC
Current consumption
(max)
700 mA 360 mA 170 mA 800 mA 120 mA 90mA
Power consumption 7,5 W 9,5 W 7,5 W 30 VA 14,5 VA 21,5 VA
Duty cycle 100%
Connection terminal 0,14 - 2,5mm² / AWG24 - AWG 14 (stranded)
Protection system IP66 (EN60529), Type 4 & 4x
Protection class
II Double insulated equipment
Operating temperature -40°C…+55°C
Storage temperature -40°C…+70°C
Max. rel. Humidity 90%
Cable entry 4x M20 (prepared)
Sealing range of
grommet
7 – 13 mm
With the use of cable diameters <7 mm, a cable screw joint
with sufficient ingress protection must be provided
Material of housing PC/ABS Blend
Material of lens PC
Installation position arbitrary
Options -SSM (see page 4)
Accessory Sealing plug (Art-no. 28300000002)
Lens colours clear, white, yellow, amber, red, green, blue
Approvals
Approvals
(valid for marked equipment)
Construction Product
Directive
(89/106/EWG)
VdS 0786-CPD-21219
Options –SSM (24V DC only)
Rated voltage 24V DC 48V DC
Operating voltage range
acc. to EN54-23
18V – 30V 40 – 57V DC
Lens colours red, clear
Signalling area EN 54-23 Category O: see document 30320-005-1
Environmental
protection class
Type B
Installation position see document 30303-005-1
The test was performed using the provided diaphragm nipples and the outer fixing holes.
VdS
G212186, data see Construction Product Directive (89/106/EWG)
GL
61062-13 HH Environmental Category C, H, EMC1
Rated Voltage Visual Signal Appliance - General Signaling Equipment - UEES, UEES7
UL, cUL
115V AC
230V AC
24V AC
12V DC
24V DC
48V DC
Suitable for indoor and outdoor use.
Warning: Not to be used as a Visual Public Mode Alarm Notification Appliance.
According to CSA-C22.2 No. 205-M1983 clause 4.3.4 the connection is limited to max.
three leads.
PYRA Xenon beacons PY X-S-05 comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules
Content of package:
1x Alarm device
1x Diaphragm nipple M20
1x Operating instruction
1x Resistor (only –SSM)
44.1 [1.74"]
35.4
[1.39"]
25.3
[1"]
13
[0.51"]
50 [1.97"]
26.8 [1.06"]
35.4
[1.39"]
60
[2.36"]
Hole pattern in the
inside of housing
Commentaires sur ces manuels